Table 1-2 Tubing Data for Models Models Tubing Data Tubing size Liquid tube in. (mm) outer diameter Gas tube in. (mm) Limit of tubing length (ft.) Limit of elevation difference between the 2 units Outdoor unit is placed higher (ft.) Outdoor unit is placed lower (ft.) Max. allowable tubing length at shipment (ft.) Required additional refrigerant *1 (oz./ft.) Refrigerant charged at shipment (lbs.) C(H)2672R 3/8 (9.52) 5/8 (15.88) 165 100 50 10 - 100 a) 0.43 4.2 C(H)3072R C(H)3672R 3/8 (9.52) 5/8 (15.88) 165 100 50 10 - 100 b) 0.43 6.2 No additional charge of compressor oil is necessary. *1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft. 1. Specifications C(H)4272R 3/8 (9.52) 5/8 (15.88) 165 100 50 10 - 100 b) 0.43 7.9 Table 1-3 List of Connection Tube Sizes Main tubing (L) Type capacity of indoor units 26 - 42 Gas tube ø5/8" 1 Liquid tube ø3/8" Amount of additional charge per 1 ft. 0.43 oz. 2 3 4 5 6 SM831148 I-87