Sanyo 26KHHS72R Service Manual - Page 90
Specifications, Installation Instructions, Tubing Length, Single type
![]() |
View all Sanyo 26KHHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 90 highlights
1-11 Installation Instructions Tubing Length Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2. 1. Specifications Single Maximum length H1 Table 1-1 Indoor unit type Maximum length Charge-less tubing length (actual length) Additional charge per 1 ft. 26, 30, 36 types 42 type 165 ft. 165 ft. 10 - 100 ft. 15 - 100 ft. 0.43 oz. 1 Maximum indoor-outdoor If outdoor unit is higher height difference If outdoor unit is lower H1 H1 < 100 < 50 2 3 4 5 6 SM831148 I-86