HIC-CH4872R (42 Type) 4. Service procedures HIC-CH2672R (26, 30, 36 Type) 1 Resistance Between terminals Resistance HIC + HIC - 200 kΩ or more 2 HIC + U 300 kΩ or more HIC + V 300 kΩ or more HIC + W 300 kΩ or more HIC - U 200 kΩ or more HIC - V 200 kΩ or more HIC - W 200 kΩ or more 3 (3) [Alarm "E31"] (communications trouble within unit) IGBT short-circuit protection 4 Is "E31" displayed even after No the power voltage is reset? Normal 5 Yes Replace outdoor unit control PCB. 6 IV-10 SM831148