80
8. Specifications
Model
S3M25K
S3M30K
S3M50K
S3M60K
S3M80K
S3M100K
OVERVIEW
Capacity
25 kVA/25 kW
30 kVA/30 kW
50 kVA/50 kW
60 kVA/60 kW
80 kVA/80 kW
100 kVA/100 kW
Topology
True On-Line Double Conversion; Voltage- and Frequency-Independent (VFI)
INPUT
Voltage and Phase
208/220V (Ph-Ph); 120/127V (Ph-N); 3-Phase, Neutral and Ground
Voltage Range
-20%, +25% (Ph-Ph 166–260V or 176–275V) at 100% Load; -40%, +25% (Ph-Ph 125–260V or 132–275V) at <50% Load
Frequency (Range)
50/60 Hz, Selectable (40 – 70 Hz)
Power Factor
≥
0.99 (100% Linear Load);
≥
0.98 (50% Linear Load)
Harmonic Distortion
< 3% THDi (100% Load)
Dual AC Input
Yes
Backfeed Protection
Yes
OUTPUT
Voltage and Phase
208/220V (Ph-Ph);
120/127V (Ph-N); 3-Phase, Neutral and Ground
AC Voltage Regulation
±1% of Nominal (Double-Conversion Mode, Converter Mode or Battery Mode); ±10% of Nominal (ECO Mode)
Power Factor
1.0 (Unity Output Power Factor)
Frequency
Selectable ±1%, ±2%, ±4%, ±5%, ±10% of Input (Default: ±5%)
Frequency Regulation
±0.1 Hz (Converter Mode or Battery Mode)
Overload (AC Mode)
Load
≤
110%=1 hour; Load
≤
125%=10 min.; Load
≤
150%=1 min.; Load >150%=Bypass
Crest Factor
3:1 Maximum
Harmonic Distortion
≤
2% THD (100% Linear Load);
≤
5% THD (100% Non-Linear Load)
Waveform
Pure Sine Wave
Transfer Time
0 ms (Line ‹–› Battery and Inverter ‹–› Bypass); <8 ms (Battery ‹–› ECO)
Parallel Capability
Parallel up to 5N+1 Units for Increased Capacity or up to 6 for Redundancy
BYPASS
Bypass Voltage Range
Upper Limit: +10%, +15%, +20% or +25% (Default: +20%); Lower Limit: -10%, -20%, -30% or -40% (Default: -40%)
Bypass Frequency Range
±10% (Adjustable)
EFFICIENCY
Online Mode
up to 94%
ECO Mode
up to 98%
BATTERY AND CHARGER
DC Acceptance Voltage
±120V DC (Nominal)
Battery Configuration
External Only*
External Only*
External Only*
External Only*
External Only*
External Only*
Internal Battery Quantity
None
None
None
None
None
None
Run time (100% Load)
UPS runtime depends on the connected loads and the battery pack/cabinet model. Refer to the model page at tripplite.com for runtimes.
Run time (50% Load)
External Battery Pack (Cabinet)
Models
*Refer to section
3.9 UPS to Cabinet Model Compatibility
Charging Current (Default)
1 – 20A (0.15C)
2 – 20A (0.15C)
4 – 40A (0.15C)
4 – 40A (0.15C)
6 – 60A (0.15C)
8 – 80A (0.15C)
ENVIRONMENT
Operating Temperature
0 – 40˚ C
Storage Temperature
-15 – 60˚ C
Operating Humidity
0 – 95% (Non-Condensing)
Operating Altitude
< 1000 m (Derate output power by 1% per 100 m above 1000 m.)
Audible Noise at 1 m
< 65.4 dBA
< 67.8 dBA
< 72 dBA
< 72 dBA
< 74 dBA
< 75.6 dBA
Heat Dissipation (100% Load)
6339 BTU/h
7679 BTU/h
12628 BTU/h
15154 BTU/h
19932 BTU/h
24915 BTU/h
MANAGEMENT
Display Panel
Large 12.7 cm (5-inch) Multi-language Touchscreen Display with Supplemental LEDs
Communications
Optional SNMP Network Management Card (
WEBCARDLX
) and three integrated MODBUS Ports: RS-232, RS-485 (RJ45), USB.
The Relay I/O card is optional.
STANDARDS
Safety
UL1778:2014 (5th Edition); CAN/CSA-C22.2 No. 107.3-14 (3rd Edition)
EMC/EMI
FCC Part 15B Class A
Additional
ENERGY STAR 2.0, RETIE, IP20 Ingress Protection Rating; RoHS, ISTA 3B/Vibration, Shock and Tip tested.
PHYSICAL
Unit Dimensions (H x W x D)
39.4 x 11.8 x 31.5 inches/
1000 x 300 x 800 mm
47.2 x 17.4 x 33.46 inches/
1200 x 442 x 850 mm
62.99 x 23.62 x 33.46 inches/
1600 x 600 x 850 mm
Unit Weight
209 lb. / 95 kg
212 lb. / 96 kg
353 lb. / 160 kg
364 lb. / 165 kg
624 lb. / 283 kg
708 lb. / 321 kg