Tripp Lite SV20KM1P1B Owners Manual for SmartOnline 208V SV-Series 3-Phase Mod - Page 14
AC Input and Output Maximum Current & Power Cable Configuration, DC Input Maximum Current
View all Tripp Lite SV20KM1P1B manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
7. Installation AC Input and Output Maximum Current & Power Cable Configuration Note: Use copper wire with minimum temperature rating of 221°F (105°C). Small-Frame Units (30U) including Battery Module(s) Recommended Installation Breaker Size Max Current Power and Ground Cable Fixation Torque Force 20kVA 250A 60A 250 MCM 120 mm2 2.26 N·m 40kVA 250A 120A 250 MCM 120 mm2 2.26 N·m Medium-Frame Units (42U) including Battery Module(s) Recommended Installation Breaker Size Max Current Power and Ground Cable Fixation Torque Force 20kVA 300A 60A 300 MCM 150 mm2 2.26 N·m 40kVA 300A 120A 300 MCM 150 mm2 2.26 N·m 60kVA 300A 180A 300 MCM 150 mm2 2.26 N·m Large Frame (42U) without Battery Modules Recommended Installation Breaker Size Max Current Power and Ground Cable Fixation Torque Force 20kVA 600A 60A 600 MCM 300 mm² 2.26 N·m 40kVA 600A 120A 600 MCM 300 mm² 2.26 N·m 60kVA 600A 180A 600 MCM 300 mm² 2.26 N·m 80kVA 600A 240A 600 MCM 300 mm² 2.26 N·m 100kVA 600A 300A 600 MCM 300 mm² 2.26 N·m 60kVA 250A 180A 250 MCM 120 mm2 2.26 N·m 80kVA 300A 240A 300 MCM 150 mm2 2.26 N·m 120kVA 600A 360A 600 MCM 300 mm² 2.26 N·m 140kVA 600A 420A 600 MCM 300 mm² 2.26 N·m DC Input Maximum Current and Power Cable Configuration Nominal Battery Voltage: +/-120V DC Small Frame (30U) including Battery Module(s) Recommended External Battery Breaker Power and Ground Cable Fixation Torque Force 20kVA 100A 3 AWG 25 mm2 2.26 N·m 40kVA 200A 4/0 AWG 95 mm2 2.26 N·m 60kVA 300A 300 MCM 150 mm2 2.26 N·m Medium Frame (42U) including Battery Module(s) Recommended External Battery Breaker Power and Ground Cable Fixation Torque Force 20kVA 100A 3 AWG 25 mm2 2.26 N·m 40kVA 200A 4/0 AWG 95 mm2 2.26 N·m 60kVA 300A 300 MCM 150 mm2 2.26 N·m 80kVA 400A 600 MCM 300 mm2 2.26 N·m Large Frame (42U) without Battery Modules Recommended External Battery Breaker Power and Ground Cable Fixation Torque Force 20kVA 100A 3 AWG 25 mm2 2.26 N·m 40kVA 200A 4/0 AWG 95 mm2 2.26 N·m 60kVA 300A 300 MCM 150 mm2 2.26 N·m 80kVA 400A 500 MCM 240 mm2 2.26 N·m 100kVA 500A 250 MCM x 2 120 mm2 x 2 2.26 N·m 120kVA 600A 300 MCM x 2 150 mm2 x 2 2.26 N·m 140kVA 700A 500 MCM x 2 240 mm2 x 2 2.26 N·m 14