Tripp Lite SV20KM1P1B Owners Manual for SmartOnline 208V SV-Series 3-Phase Mod - Page 35
Technical Specifications
View all Tripp Lite SV20KM1P1B manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 35 highlights
13. Technical Specifications MODEL CAPACITY TOPOLOGY 20K 40K 60K 80K 100K 120K 140K 20kVA/18kW 40kVA/36kW 60kVA/54kW 80kVA/72kW 100kVA/90kW 120kVA/108kW 140kVA/126kW Voltage and Frequency Independent (VFI) True on-line Double Conversion INPUT Voltage Voltage Range (Ph-N) Phase Operating Frequency Frequency Range Power Factor THDi Inverter Bridge 208/220V (Ph-Ph), 120/127V (Ph-N) 90V to 146V (100% load) / 70V to 89V (70% load) 3-phase, neutral and ground 50/60Hz (selectable) 40Hz ~ 70Hz ± 0.1Hz >0.99% 150%: 200 ms 3:1 92% >98% 32 to 104°F / 0 to 40°C (Output capacity will be de-rated 90% when temperature is 88~95°F / 31~35°C; will be de-rated to 80% when temperature is 96~104°F / 36~40°C) 5 to 140°F / -15 to 60°C 0 to 95% (non-condensing)
35
13. Technical Specifications
MODEL
20K
40K
60K
80K
100K
120K
140K
CAPACITY
20kVA/18kW
40kVA/36kW
60kVA/54kW
80kVA/72kW
100kVA/90kW
120kVA/108kW
140kVA/126kW
TOPOLOGY
Voltage and Frequency Independent (VFI) True on-line Double Conversion
INPUT
Voltage
208/220V (Ph-Ph), 120/127V (Ph-N)
Voltage Range (Ph-N)
90V to 146V (100% load) / 70V to 89V (70% load)
Phase
3-phase, neutral and ground
Operating Frequency
50/60Hz (selectable)
Frequency Range
40Hz ~ 70Hz ± 0.1Hz
Power Factor
>0.99%
THDi
<3%
Inverter Bridge
IGBT technology
OUTPUT
Voltage
208/220V (3ph, 4 wire, neutral reference to bypass neutral)
AC Voltage Regulation
<1% (balanced load)
Frequency
50/60Hz (selectable)
Frequency Range
40Hz ~ 70Hz ± 0.1Hz
Overload
AC mode
105-110%: 60 min.
111-125%: 10 min.
126-150%: 1 min.
>150%: 200 ms
Battery mode
105-110%: 60 min.
111-125%: 10 min.
126-150%: 1 min.
>150%: 200 ms
Crest Factor
3:1
Harmonic Distortion
<2% (100% linear load); <4% (100% non-linear load)
Output Waveform
Pure sine wave
BYPASS
Automatic Bypass
Standard
Manual Maintenance Bypass
Standard
Transfer Time
0 ms
Default Bypass Voltage Tolerance
+15/-20%
Overload
105 to 110%: 60 min.
111 to 125%: 10 min.
126 to 150%: 1 min.
>150%: 200 ms
BATTERY
Battery Type*
Maintenance-free sealed valve-regulated lead acid (VRLA)
Battery Capacity*
18Ah (per battery module)
Float Voltage
2.3V/cell
Boost Voltage
2.35V/cell
End of Discharge Voltage
1.67V/cell
Battery Storage Time*
6 months (without recharge, 77°F / 25°C)
Battery Charger Capacity
8A (per power module)
ENVIRONMENT
Efficiency (Inverter Mode)
>92%
Efficiency (ECO Mode)
>98%
Operating Temperature
32 to 104°F / 0 to 40°C (Output capacity will be de-rated 90% when temperature is 88~95°F / 31~35°C;
will be de-rated to 80% when temperature is 96~104°F / 36~40°C)
Storage Temperature (Excl Battery Module)
5 to 140°F / -15 to 60°C
Operating Humidity
0 to 95% (non-condensing)
Operating Altitude
<3280 ft. / <1000 m (1% derating per 328 ft. / 100 m above 3280 ft. / <1000 m)
Audible Noise
<75dBA
Protection Degree
IP20
Color
RAL 9005 (Black)
* Applies to Small- and Medium-Frame systems with internal battery modules.