Tripp Lite SV20KM1P1B Owners Manual for SmartOnline 208V SV-Series 3-Phase Mod - Page 24

Setup Screen

Page 24 highlights

9. Control Panel Battery Positive Voltage (V) Battery positive voltage, Units 0.1V Negative Voltage (V) Battery negative voltage, Units 0.1V Positive Current (A) Battery positive current, Units 0.1A Battery Negative Current (A) Battery negative current, Units 0.1A Remain Time (Min) Battery runtime remaining, Units 1 minute Capacity (%) Percentage of battery capacity remaining, Units 1% Test Result Battery test result Charging Status Battery charging status (settable per section 9.3.4 Control Screen) 9.3.6 Setup Screen Use "Down/Right" key to select "Setup" option. A password is required to access the menu sub-screen. Default password is 0000. GENERAL HOME MENU SETUP Enter Password SYSTEM BATTERY PRE-ALARM 9.3.6.1 General The SETUP - GENERAL screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table 9.3 for details. The Maintenance password (9999) is required for settings marked with *. Time* Change Password Set current time / system install date / system latest maintenance date / battery install date / battery latest maintenance date Set new password Audible Alarm Set "Disable" or "Enable" (default: Enabled) GENERAL Factory Reset* EEPROM Reset* Restore to factory default settings Set EEPROM default EPO Function* Set EPO "Normal Close Active" or "Normal Open Active"; Default: Normal Open Active Save Setting* Save EEPROM setting 24

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112

24
Battery
Battery
Positive Voltage (V)
Negative Voltage (V)
Positive Current (A)
Negative Current (A)
Remain Time (Min)
Capacity (%)
Test Result
Charging Status
9.3.6 Setup Screen
Use “Down/Right” key to select “Setup” option. A password is required to access the menu sub-screen. Default password is 0000.
PRE-ALARM
BATTERY
SYSTEM
GENERAL
HOME
MENU
SETUP
Enter Password
9.3.6.1 General
The SETUP – GENERAL screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to
table 9.3 for details. The Maintenance password (9999) is required for settings marked with *.
GENERAL
Time*
Change Password
Audible Alarm
Factory Reset*
EEPROM Reset*
EPO Function*
Save Setting*
9. Control Panel
Battery positive voltage, Units 0.1V
Battery negative voltage, Units 0.1V
Battery positive current, Units 0.1A
Battery negative current, Units 0.1A
Battery runtime remaining, Units 1 minute
Percentage of battery capacity remaining, Units 1%
Battery test result
Battery charging status (settable per section 9.3.4 Control Screen)
Set current time / system install date / system latest maintenance date / battery install
date / battery latest maintenance date
Set new password
Set “Disable” or “Enable” (default: Enabled)
Restore to factory default settings
Set EEPROM default
Set EPO “Normal Close Active” or “Normal Open Active”; Default: Normal Open Active
Save EEPROM setting