HP Integrity Superdome SX2000 Windows Integrity Management Agents Reference - Page 42

No Cabinet Start, Insufficient IO Fans Probable Cause: The number of IO fans required

Page 42 highlights

Event ID Event Severity Event Description 7784 Error No Cabinet Start, Insufficient IO Fans Probable Cause: The number of IO fans required is a hard number. It is not dependent upon the number of entities installed in a Cabinet. The Utilities Subsystem is not allowing the cabinet to power up due to an insufficient number of installed IO fans. Recommended Action: Install missing IO fans, or if proper number installed, troubleshoot IO fan presence detection. SNMP Trap: hpevtAbortStartIofan - 7784 in HPIFPTRAP.MIB. 7786 Warning AC power to the PDCA was removed. Data Byte 3 specifies PDCA number. Probable Cause: Power source supplying AC to the PDCA has failed. Recommended Action: Troubleshoot AC power problem. SNMP Trap: hpevtAcDeleted - 7786 in HPIFPTRAP.MIB. 7791 Warning Cabinet Main Blower Failed Probable Cause: Cabinet Blower Failed Recommended Action: Replace failed blower module as soon as possible following the Blower Module Remove and Replace Procedures. SNMP Trap: hpevtBlowrFail - 7791 in HPIFPTRAP.MIB. 7793 Warning 48 Volt Converter Failed. Data Byte 3 specifies PDCA number. Probable Cause: The PDCA identified has failed. This will be evident by many BPS_FAIL codes and probably a AC_DELETED code in the Event Log. Recommended Action: Contact HP Support personnel to troubleshoot problem SNMP Trap: hpevtBpsFail48flt - 7793 in HPIFPTRAP.MIB. 7795 Warning Fan failed in designated Bulk Power Supply Probable Cause: Fan failure or fan obstructed Recommended Action: If fan is obstructed, remove obstruction. If no obstruction, Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtBpsFailFanflt - 7795 in HPIFPTRAP.MIB. 7796 Warning 1 Side Converter Over Temp Probable Cause: If this code is not accompanied by other codes pointing to the same Bulk Power Supply, then it is an internal component failure. Recommended Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtBpsFailOt - 7796 in HPIFPTRAP.MIB. 7798 Warning Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to the cabinet, increasing the estimated Power Consumption. Or, a non-functional GSP bus entity has become functional, providing previously missing power consumption information. Recommended Action: Purchase and install a Bulk Power Supply, if redundancy is desired. SNMP Trap: hpevtBpsNotRedundant - 7798 in HPIFPTRAP.MIB. 7799 Error +48V DC has exceeded its upper limit Probable Cause: The cabinet's 48V power has exceeded an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtBpsOvervoltage - 7799 in HPIFPTRAP.MIB. 7803 Error +48V DC has fallen below its lower limit Probable Cause: The cabinet's 48V power has fallen below an acceptable lower threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtBpsUndervoltage 7803 in HPIFP 7806 Warning Cabinet Fan Failed Probable Cause: Cabinet Fan Failed Recommended Action: Replace failed cabinet fan module as soon as possible following the Cabinet Fan Module Remove and Replace Procedures. SNMP Trap: hpevtCabFanFail - 7806 in HPIFPTRAP.MIB. 7822 Error Housekeeping power has exceeded expected levels. Probable Cause: The cabinet's housekeeping power has risen above an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtHkpOvervoltage - 7822 in HPIFPTRAP.MIB. 7823 Error Housekeeping power has fallen below expected levels. Probable Cause: The cabinet's housekeeping power has fallen below an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap: hpevtHkpUndervoltage - 7823 in HPIFPTRAP.MIB. 42 Management Agents Event Tables

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127

Event Description
Event Severity
Event ID
No Cabinet Start, Insufficient IO Fans Probable Cause: The number of IO fans required
is a hard number. It is not dependent upon the number of entities installed in a
Cabinet. The Utilities Subsystem is not allowing the cabinet to power up due to an
insufficient number of installed IO fans. Recommended Action: Install missing IO
fans, or if proper number installed, troubleshoot IO fan presence detection. SNMP
Trap: hpevtAbortStartIofan - 7784 in HPIFPTRAP.MIB.
Error
7784
AC power to the PDCA was removed. Data Byte 3 specifies PDCA number. Probable
Cause: Power source supplying AC to the PDCA has failed. Recommended Action:
Troubleshoot AC power problem. SNMP Trap: hpevtAcDeleted - 7786 in
HPIFPTRAP.MIB.
Warning
7786
Cabinet Main Blower Failed Probable Cause: Cabinet Blower Failed Recommended
Action: Replace failed blower module as soon as possible following the Blower
Module Remove and Replace Procedures. SNMP Trap: hpevtBlowrFail - 7791 in
HPIFPTRAP.MIB.
Warning
7791
48 Volt Converter Failed. Data Byte 3 specifies PDCA number. Probable Cause: The
PDCA identified has failed. This will be evident by many BPS_FAIL codes and
probably a AC_DELETED code in the Event Log. Recommended Action: Contact HP
Support personnel to troubleshoot problem SNMP Trap: hpevtBpsFail48flt - 7793 in
HPIFPTRAP.MIB.
Warning
7793
Fan failed in designated Bulk Power Supply Probable Cause: Fan failure or fan
obstructed Recommended Action: If fan is obstructed, remove obstruction. If no
obstruction, Contact HP Support personnel to troubleshoot problem. SNMP Trap:
hpevtBpsFailFanflt - 7795 in HPIFPTRAP.MIB.
Warning
7795
1 Side Converter Over Temp Probable Cause: If this code is not accompanied by
other codes pointing to the same Bulk Power Supply, then it is an internal component
failure. Recommended Action: Contact HP Support personnel to troubleshoot
problem. SNMP Trap: hpevtBpsFailOt - 7796 in HPIFPTRAP.MIB.
Warning
7796
Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to the
cabinet, increasing the estimated Power Consumption. Or, a non-functional GSP bus
entity has become functional, providing previously missing power consumption
information. Recommended Action: Purchase and install a Bulk Power Supply, if
redundancy is desired. SNMP Trap: hpevtBpsNotRedundant - 7798 in
HPIFPTRAP.MIB.
Warning
7798
+48V DC has exceeded its upper limit Probable Cause: The cabinet's 48V power has
exceeded an acceptable upper threshold. Recommended Action: Contact HP Support
personnel to troubleshoot problem. SNMP Trap: hpevtBpsOvervoltage - 7799 in
HPIFPTRAP.MIB.
Error
7799
+48V DC has fallen below its lower limit Probable Cause: The cabinet's 48V power
has fallen below an acceptable lower threshold. Recommended Action: Contact HP
Support personnel to troubleshoot problem. SNMP Trap: hpevtBpsUndervoltage -
7803 in HPIFP
Error
7803
Cabinet Fan Failed Probable Cause: Cabinet Fan Failed Recommended Action: Replace
failed cabinet fan module as soon as possible following the Cabinet Fan Module
Remove and Replace Procedures. SNMP Trap: hpevtCabFanFail - 7806 in
HPIFPTRAP.MIB.
Warning
7806
Housekeeping power has exceeded expected levels. Probable Cause: The cabinet's
housekeeping power has risen above an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap:
hpevtHkpOvervoltage - 7822 in HPIFPTRAP.MIB.
Error
7822
Housekeeping power has fallen below expected levels. Probable Cause: The cabinet's
housekeeping power has fallen below an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. SNMP Trap:
hpevtHkpUndervoltage - 7823 in HPIFPTRAP.MIB.
Error
7823
42
Management Agents Event Tables