AI Module Value Representation, Underflow LED
View all Motorola V186 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 38 highlights
Analog Input Modules AI Module Value Representation: In ± 20 mA current inputs Decimal Value < -32256 -32000 0 32000 > 32256 Input Current < -20.16 mA -20 mA 0 mA +20 mA > +20.16 mA Indication Underflow LED ON Rated range (no LED active) Overflow LED ON In 4 - 20 mA current inputs Decimal Value < 6144 6400 0 32000 > 32256 Input Current < 3.84 mA +4 mA 0 mA +20 mA > +20.16 mA Indication Underflow LED ON Rated range (no LED active) Overflow LED ON In ± 5 V current inputs Decimal Value < -32256 -32000 0 32000 > 32256 Input Voltage +5.04 V Indication Underflow LED ON Rated range (no LED active) Overflow LED ON In 0 - 5 V current inputs Decimal Value < -256 0 32000 > 32256 Input Voltage < -0.04 V 0 V +5 V > +5.04 V Indication Underflow LED ON Rated range (no LED active) Overflow LED ON In 1 - 5 V current inputs Decimal Value < 6144 6400 32000 > 32256 Input Voltage < 0.96 V 1 V +5 V > 5.04 V Indication Underflow LED ON Rated range (no LED active) Overflow LED ON 34