In the Hardware Test utility, it is possible to set the module to Freeze Mode. In this mode
View all Motorola V186 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 51 highlights
Digital Output and Digital Input FET Modules Parameter DO Mask Selection No /Yes Default Setup No Per Module/ Parameter Setup Input Location Output Application Programmer I/O link table Each DO/DI module can be switched by the user application program to Sleep Mode. In Sleep Mode, the module does not function and the power consumption is minimized. During Sleep mode, the user application program will get the KLV or PDV per each DI. In the event of a DO/DI module failure, the ERR LED on the module will be lit. This event is registered by the CPU in the Error Logger. DO/DI module failure status is also visible to the user application program. The DO/DI module can be diagnosed and monitored using the STS Hardware Test utility. The Hardware Test verifies that the module is operational, presents the module configuration and shows the actual value of each input and output. It is also possible to change the input filter setup for the duration of the Hardware test and change the value of the DOs. In the Hardware Test utility, it is possible to set the module to Freeze Mode. In this mode the user application program will get the KLV/PDV of each input in the module instead of the actual input value. The DO values will keep the last value they had when the module was switched to Freeze Mode. Freeze mode enables testing the inputs and outputs while the user application program is running. 47