Dell PowerEdge T40 EMC Installation and Service Manual - Page 85

Thermal restriction matrix, Particulate and gaseous contamination specifications

Page 85 highlights

Thermal restriction matrix Table 37. Thermal restrictions matrix Ambient Processor DIMM Drive 25°C No restriction No restriction 30°C No restriction No restriction Limited to entry drives with power less than 6.8W Or No restriction to 1 / 2 TB 7200 rpm and 4 TB 5400 rpm 35°C No restriction No restriction NOTE: The PowerEdge T40 does not support enterprise-class drives. Card Limited to Tier 2 PCIe cards Or PCIe cards do not require system level cooling assistance up to a local ambient temperature of 55°C Particulate and gaseous contamination specifications Table 38. Particulate contamination specifications Particulate contamination Specifications Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and non-data center environments. Corrosive dust Air must be free of corrosive dust. Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and non-data center environments. Table 39. Gaseous contamination specifications Gaseous contamination Copper coupon corrosion rate Silver coupon corrosion rate Specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95

Thermal restriction matrix
Table 37. Thermal restrictions matrix
Ambient
25°C
30°C
35°C
Processor
No restriction
No restriction
No restriction
DIMM
No restriction
No restriction
No restriction
Drive
Limited to entry drives with power less than 6.8W
Or
No restriction to 1 / 2 TB 7200 rpm and 4 TB 5400 rpm
NOTE:
The PowerEdge T40 does not support enterprise-class drives.
Card
Limited to Tier 2 PCIe cards
Or
PCIe cards do not require system level cooling assistance up to a local ambient temperature of 55°C
Particulate and gaseous contamination specifications
Table 38. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence
limit.
NOTE:
This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
This condition applies to data center and non-data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center environments.
Table 39. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
Silver coupon corrosion rate
<200 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Technical specifications
85