HP LH4r HP Netserver LH 3/3r User Guide - Page 16
Power-On Tests
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
Chapter 2 Controls, Ports, and Indicators • In Europe: ◊ For a single NetServer in a rack, use a 15-amp-minimum circuit with one IEC MCB C-type breaker for each 16-amp PDU. ◊ For multiple NetServers in a rack, use a 15-amp-minimum circuit with one IEC MCB D-type breaker for each 16-amp power distribution unit. Each 16-amp PDU can accommodate a maximum of two NetServers. When the proper power supply is available, connect the NetServer to the AC power source. Power-On Tests The NetServer runs a set of diagnostic tests when it is first connected to a power source. If the NetServer passes the tests, you will see: HP NetServer LH 3 If the NetServer does not pass the tests, you will see: Display now? Press Enter to view the error message. Write the error message down and refer to "POST Codes" in Chapter 12, "Troubleshooting." 8