Panasonic WV-ST165 Operating Instructions - Page 142

Change the AUX name [Alarm], AUX title

Page 142 highlights

13 Configure the alarm settings [Alarm] • Pulse: When an alarm is detected, the alarm output terminal will be in the state to the "Trigger output" setting for the period set for "Pulse width". When the alarm occurrence indication button is clicked, the alarm output terminal will return to the normal state. • Default: Latch [Trigger output] Select "Open" or "Close" to determine whether to open or close the alarm output terminal when outputting the alarm signals. • Open: The alarm output terminal will open when outputting the alarm signals. (Normally close) • Close: The alarm output terminal will close when outputting the alarm signals. (Normally open) • Default: Close Note • When "Open" is selected, the alarm signal will be output for about 20 seconds when the power of the unit is turned on. [Pulse width] When "Pulse" is selected for "Alarm output", select an alarm output terminal duration from the following. • Available range: 1-120s • Default: 1s 13.6 Change the AUX name [Alarm] Click the [Alarm] tab on the "Alarm" page. (®page 47, page 49) The names of "AUX", "Open" and "Close" on the "Live" page can be changed. AUX title [AUX (Up to 10 characters)] Enter the name for "AUX" on the "Live" page. • Unavailable characters: " & • Default: AUX [Open (Up to 5 characters)] Enter the name for "Open" of "AUX" on the "Live" page. • Unavailable characters: " & • Default: Open [Close (Up to 5 characters)] Enter the name for "Close" of "AUX" on the "Live" page. • Unavailable characters: " & • Default: Close 142 Operating Instructions

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216
  • 217
  • 218
  • 219
  • 220
  • 221
  • 222
  • 223
  • 224
  • 225
  • 226
  • 227
  • 228
  • 229
  • 230
  • 231
  • 232
  • 233
  • 234
  • 235
  • 236
  • 237
  • 238
  • 239
  • 240
  • 241
  • 242
  • 243
  • 244

Pulse:
When an alarm is detected, the alarm output terminal will be in the state to the “Trigger output”
setting for the period set for “Pulse width”. When the alarm occurrence indication button is clicked, the
alarm output terminal will return to the normal state.
Default:
Latch
[Trigger output]
Select “Open” or “Close” to determine whether to open or close the alarm output terminal when outputting the
alarm signals.
Open:
The alarm output terminal will open when outputting the alarm signals. (Normally close)
Close:
The alarm output terminal will close when outputting the alarm signals. (Normally open)
Default:
Close
Note
When “Open” is selected, the alarm signal will be output for about 20 seconds when the power of the
unit is turned on.
[Pulse width]
When “Pulse” is selected for “Alarm output”, select an alarm output terminal duration from the following.
Available range:
1-120s
Default:
1s
13.6
Change the AUX name [Alarm]
Click the [Alarm] tab on the “Alarm” page. (
®
page 47, page 49)
The names of “AUX”, “Open” and “Close” on the “Live” page can be changed.
AUX title
[AUX (Up to 10 characters)]
Enter the name for “AUX” on the “Live” page.
Unavailable characters:
" &
Default:
AUX
[Open (Up to 5 characters)]
Enter the name for “Open” of “AUX” on the “Live” page.
Unavailable characters:
" &
Default:
Open
[Close (Up to 5 characters)]
Enter the name for “Close” of “AUX” on the “Live” page.
Unavailable characters:
" &
Default:
Close
142
Operating Instructions
13 Configure the alarm settings [Alarm]