Tripp Lite SU10KRT3U Owner's Manual for SmartOnline Single-Phase 10kVA UPS 932 - Page 20
Bypass Messages, Shutdown Messages
View all Tripp Lite SU10KRT3U manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
Operation continued Bypass Messages While in BYPASS mode, the UPS system monitors utility input voltage and supplies filtered AC power to connected equipment. If utility voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS system reports the condition on the control panel's LCD and stops supplying AC power to connected equipment. If utility voltage returns to an acceptable level, the UPS system resumes supplying AC power to connected equipment and the control panel's LCD reports that output voltage was too high or too low at one time, but has returned to nominal. Shutdown Messages The UPS system will shut down and the control panel's LCD will display a message if it detects one of the following conditions. Note: During all these conditions, the "Input," "Output" and "Bypass" LEDs will illuminate. SHUTDOWN CONDITION Remote Shutdown Command via DB9 Remote Shutdown Command via EPO LCD MESSAGE SHUT DOWN REMOTE COMMAND SHUT DOWN EMERGENCY STOP! 20 201102089 93-2982.indb 20 7/11/2011 3:49:32 PM