Tripp Lite SU10KRT3U Owner's Manual for SmartOnline Single-Phase 10kVA UPS 932 - Page 23
Output Settings - Voltage, Output Settings - Frequency Converter
View all Tripp Lite SU10KRT3U manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Operation continued UPS Settings continued Output Settings - Voltage Note: Any output settings change requires a UPS power cycle. From the SETUP MENU screen, scroll DOWN to reach the OUTPUT SETTING screen. Press ON to access the OUTPUT VOLTAGE screen, then press ON again. Scroll UP or DOWN to choose among 5 voltage values: 200V, 208V, 220V, 230V or 240V. Press ON to save the setting. The default setting is 208V. * * Note: This is the default screen. Output Settings - Frequency Converter From the SETUP MENU screen, scroll DOWN to reach the OUTPUT SETTING screen. Press ON to access the OUTPUT VOLTAGE screen, then press DOWN to access the FREQ CONVERTER screen, then press ON. Scroll UP or DOWN to choose among 3 settings: DISABLE, 50 Hz or 60 Hz. Press ON to save the selection. When the FREQ CONVERTER function is disabled, the UPS system will automatically detect input frequency and select 50 Hz or 60 Hz to match the input. The default setting is DISABLE. Note: It is recommended that you leave the Frequency Converter in DISABLE mode when using the 10K Transformer. 23 201102089 93-2982.indb 23 7/11/2011 3:49:33 PM