Tripp Lite SU10KRT3U Owner's Manual for SmartOnline Single-Phase 10kVA UPS 932 - Page 9

High Voltage Warnings - power supply

Page 9 highlights

Connection continued Connect Transformer to AC Output Circuit 1 Pass user-supplied cabling through the junction box's left knockout (1.25" diam.) and connect it to the transformer's AC A output terminals A . 2 Refer to the AC output voltage labeling above the transformer's AC output terminals A to determine which terminal connections will provide voltage appropriate for your equipment. Connect the other end of the cable to the output circuit that will supply your equipment with AC power. 1 Connect Transformer to AC Power Source High Voltage Warnings Warning: Make sure the breaker for the UPS system's AC power source is turned off before proceeding. Failure to de-energize the input circuit will result in the continued risk of injury or death from contact with high voltage. 1 Pass user-supplied cabling through the junction box's middle knockout (1.25" diam.) and connect it to the transformer's AC input terminals A . Connect the other end of the cabling to the AC power source. 2 Reattach the transformer's junction box B . 3 Confirm the transformer's input voltage setting by removing the switch cover C above the input voltage selection switch. Set the switch to 208V if necessary, then reattach the switch cover. Facility Input Voltage 240V AC 208V AC (Default) 200V AC Transformer Input Voltage Setting (Rear Panel Switch) 240V AC 208V AC (Default) 240V AC Power Module Input Voltage Setting (Control Panel LCD) 240V AC 208V AC (Default) 200V AC 9 201102089 93-2982.indb 9 2 A B C A 1-3 A Transformer Detail 7/11/2011 3:49:00 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84

9
Connection
continued
Connect Transformer to AC Output Circuit
1
Pass user-supplied cabling through the junction box’s left
knockout (1.25" diam.) and connect it to the transformer’s AC
output terminals
A
.
2
Refer to the AC output voltage labeling above the transformer’s
AC output terminals
A
to determine which terminal connections
will provide voltage appropriate for your equipment. Connect the
other end of the cable to the output circuit that will supply your
equipment with AC power.
A
1
2
A
Connect Transformer to AC Power Source
High Voltage Warnings
Warning: Make sure the breaker for the UPS system’s AC power
source is turned off before proceeding. Failure to de-energize the input
circuit will result in the continued risk of injury or death from contact
with high voltage.
1
Pass user-supplied cabling through the junction box’s middle
knockout (1.25" diam.) and connect it to the transformer’s AC
input terminals
A
. Connect the other end of the cabling to the
AC power source.
2
Reattach the transformer’s junction box
B
.
3
Confirm the transformer’s input voltage setting by removing the
switch cover
C
above the input voltage selection switch. Set the
switch to 208V if necessary, then reattach the switch cover.
Facility Input
Voltage
Transformer Input Voltage Setting
(Rear Panel Switch)
Power Module Input Voltage Setting
(Control Panel LCD)
240V AC
240V AC
240V AC
208V AC (Default)
208V AC (Default)
208V AC (Default)
200V AC
240V AC
200V AC
B
C
A
1-3
Transformer Detail
A
201102089
93-2982.indb
9
7/11/2011
3:49:00 PM