Connecting 4-Wire Smoke Detectors
UPC - 046188090938
View all GE 60-806-95R-16Z manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 16 highlights
ZC O M / Z6/ 2W - 2W + Panel Terminals 1 6 17 - + - + Note The Two-Wire Smoke setting (in program mode) must be off when connecting 4-wire smoke detectors to zone 6. For UL Listed systems, 4-wire smoke detectors cannot be connected to onboard panel zone inputs. 2k Ohm EOL Resistor (49-454) Locate at Last Device Figure 10. Connecting 2-Wire Smoke Detectors Connecting 4-Wire Smoke Detectors Zone inputs 1 through 6 can be used with 4-wire smoke detectors that latch and remain in the alarm state until power is removed and then restored to the detector. The panel provides this power interruption from panel terminal 8 (OUT2/OC) provided that the output configuration number is set (in program mode) to 01500. For more information on output configuration numbers, see the section "Programming the Panel" and the tables in Appendix A. Use only 4-wire smoke detectors that operate on 8.5 to 14.2 VDC. Connect up to five Sentrol (ESL) model 449AT (ITI part no. 13-360) smoke detectors to panel power input as shown in Figure 11. 11 Installing the System