Operation 7 The STANDBY MODE selection screen will appear. STANDBY MODE screen allows users to enable the UPS to provide output power when running in standby mode. The standby mode factory configuration is NO OUTPUT. In this configuration, the screen will alternate between STANDBY MODE / PRESS ON KEY TO TURN UPS ON. Note: To enable bypass power output in standby mode, select BYPASS OUTPUT in the standby mode configuration screen. In this configuration, the screen will alternate between BYPASS MODE / PRESS ON KEY TO TURN UPS ON. To Advance to the Next Screen: Press SCROLL (v) To Change This Setting: Press "SELECT" (^) Note: The UPS must be in Standby Mode to change this setting. NO OUTPUT* SCROLL SELECT 8 The FREQUENCY CONVERTER selection screen will appear. Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: No output & Bypass output Scroll through available values and press SELECT (^) to SET. Factory default = NO OUTPUT FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to 60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility power conditions at start-up. The factory configuration of DISABLE is ideal for most applications. Some users may wish to convert frequency for connected equipment. To successfully configure your UPS for frequency conversion, ENABLE the FREQUENCY CONVERTER function and SET the OUTPUT FREQUENCY function to the desired 50 or 60 Hz setting. To Advance to the Next Screen: Press SCROLL (v) To Change This Setting: Press "SELECT" (^) Note: The UPS must be in Standby Mode to change this setting. DISABLE* SCROLL SELECT 9 The ECONOMY MODE selection screen will appear. Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: ENABLE, DISABLE Scroll through available values and press SELECT (^) to SET. Factory default = DISABLE ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output by suspending double-conversion circuits whenever input power is already of sufficient quality to run connected equipment. In economy mode, the UPS consults the current BYPASS RANGE setting (+/-5% to 10%). When input voltage strays pass the selected percentage preset, the UPS will automatically switch to on-line mode. When input voltage falls back within bypass range settings the UPS will automatically return to economy mode. Note: The suggested setting range is +/- 5% to +/- 10%. To Advance to To Change This the Next Screen: Setting: Press SCROLL (v) Press "SELECT" (^) Continued on page 20. DISABLE* SCROLL SELECT Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: ENABLE, DISABLE Scroll through available values and press SELECT (^) to SET. Factory default = DISABLE 19 13-07-015-9332C3.indb 19 7/26/2013 11:16:27 AM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80

 


NO OUTPUT*
SCROLL
SELECT
Continued on page 20.
 


DISABLE*
SCROLL
SELECT
 


DISABLE*
SCROLL
SELECT
19
Operation
7
The STANDBY MODE selection screen will appear.
STANDBY MODE screen allows users to enable the UPS to provide output power when
running in standby mode. The standby mode factory configuration is NO OUTPUT. In this
configuration, the screen will alternate between STANDBY MODE / PRESS ON KEY TO TURN
UPS ON.
Note: To enable bypass power output in standby mode, select BYPASS OUTPUT in the standby mode configuration
screen. In this configuration, the screen will alternate between BYPASS MODE / PRESS ON KEY TO TURN UPS ON.
To Change This
Setting:
Press “SELECT” (
^
)
8
The FREQUENCY CONVERTER selection screen will appear.
FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to
60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility
power conditions at start-up. The factory configuration of DISABLE is ideal for most
applications. Some users may wish to convert frequency for connected equipment. To
successfully configure your UPS for frequency conversion, ENABLE the FREQUENCY
CONVERTER function and SET the OUTPUT FREQUENCY function to the desired 50 or 60 Hz
setting.
9
The ECONOMY MODE selection screen will appear.
ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output
by suspending double-conversion circuits whenever input power is already of sufficient quality
to run connected equipment. In economy mode, the UPS consults the current BYPASS
RANGE setting (+/-5% to 10%). When input voltage strays pass the selected percentage
preset, the UPS will automatically switch to on-line mode. When input voltage falls back
within bypass range settings the UPS will automatically return to economy mode.
Note: The
suggested setting range is +/- 5% to +/- 10%.
Press “SELECT” (^) to SET this value.
Press “SCROLL” (v) to advance to the next option.
Available values are: No output & Bypass output
Scroll through available values and press
SELECT (^) to SET.
Factory default = NO OUTPUT
To Advance to
the Next Screen:
Press SCROLL (
v
)
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: ENABLE, DISABLE
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = DISABLE
To Advance to
the Next Screen:
Press SCROLL (
v
)
Note: The UPS must be
in Standby Mode to
change this setting.
Note: The UPS must be
in Standby Mode to
change this setting.
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: ENABLE, DISABLE
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = DISABLE
To Advance to
the Next Screen:
Press SCROLL (
v
)