Campbell Scientific CR10 CR10 Measurement and Control - Page 200
iniiiny
View all Campbell Scientific CR10 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 200 highlights
SECTION 14. INSTALLATION AND MAINTENANCE ln other applications it may be desirable to simply switch power to a device without going through a relay. Figure 14.10-2 illustrates a circuit for switching external power to a device without going through a relay. lf the peripheral to be powered draws in excess of 75 mA at room temperature (limit of the 2N2907A medium power transistor), the use of a relay (Figure 14.10-1) would be required. Other control port activated circuits are possible for applications with greater currenVvoltage demands than shown in Figures 14.10-1 and2. For more information contact Campbell Scientif ic's Marketing Department. SUPPLY: MAXIMUM = 40 VDC = MINIMUM REQUIRED CO|L VOLTAGE iniiiny T A \/n^ MAXIMUM CURRENT TO CO|L lS 75 mA AT 25'C, 4o mA Ar -so'c CONTROL PORT CONTROL PORT FIGURE 14.10-1. Relay Driver Circuit with Relay VDC MAXIMUM 2N22224 2N2907A MAXIMUM CURRENT TO PERIPHERAL lS 75 mA AT 25'C. 40 mA AT -50'C PERIPHERAL TO BE POWERED FfGURE 14.10-2. Power Switching without Relay 14-8