CyberPower PDU41102 User Manual 2 - Page 11
Definition, Humidity, Contact
![]() |
View all CyberPower PDU41102 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 11 highlights
Web Interface Item Hysteresis Rate of Change Unit Humidity High Threshold Low Threshold Hysteresis Rate of Change Contact Definition The point where the environmental state changes from abnormal to normal and users receive a clearing event notification. The function of Hysteresis is to avoid receiving multiple event notifications. *For high threshold, the point is the threshold minus the Hysteresis value; for low threshold, the point is the threshold plus the Hysteresis value. For example: The high threshold is 32°C, and hysteresis is 2°C. The temperature rises to 33°C, you will get a warning. Then it goes down to 31°C and up to 33°C repeatedly. No clearing events and warnings will occur while the temperature readings are within the Hysteresis. You will not get a clearing event until it drops to 30°C. Define the abnormal change of temperature per 5 minutes. For example: The current temperature is 23°C, and rate of change is 10°C. If it goes up to 33°C or down to 13°C within 5 minutes, you will get a warning. Select the unit of temperature. Set the highest humidity value for a high humidity warning. Set the lowest humidity value for a low humidity warning. Same as Hysteresis under temperature. Same as Hysteresis under temperature. Enter the name of each input dry contact relay and use the dropdown menu to define the normal status of each one. Intelligent PDU User Guide 9