oltloadcfg show, oltloadcfg index 1 overload 1800, oltloadcfg index 2 nearover 1000, oltloadcfg
View all CyberPower PDU41102 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 89 highlights
To display outlet load configuration CyberPower > oltloadcfg show Example 2: To set overload threshold of outlet #1 at 1800W CyberPower > oltloadcfg index 1 overload 1800 Example 3: To set near overload threshold of outlet #2 at 1000W CyberPower > oltloadcfg index 2 nearover 1000 Example 4: To set low load threshold of outlet #10 at 100W CyberPower > oltloadcfg index 10 lowload 100 Commad Line Interface schedule Description: Show and configure the outlet schedule of device. Option show guest index Argument 1 | 2 | 3 1 | 2 |...| schedule number | 10 add once | daily | weekly Intelligent PDU User Guide Description Show information of schedule. Set daisy chain index. Select schedule index. add - Add new schedule of outlet once - Add schedule as once frequency daily - Add schedule as daily frequency weekly - Add schedule as weekly frequency After finish this command, input schedule name and step by step. The parameters of action on | off | reboot | delayon | delayoff | delayreboot The parameters of month 1| 2| ...... |12 The Parameters of day of week Mon | Tue | Wed | Thu | Fri | Sat | Sun The Parameters of day 1| 2| 3| ...... |31 The Parameters of hour 1| 2| 3| ...... |24 87