CyberPower PDU41102 User Manual 2 - Page 25
Definition, On Near Overload, On Overload, Power Restore, ColdStart Configuration, Previous State,
View all CyberPower PDU41102 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Web Interface Item Definition Low Load Threshold Set the value for the total current on the PDU that will signal a low load warning. Must be lower than Near Overload Threshold. Outlet Restriction** When load current exceeds the corresponding threshold, no outlets will be allowed to turn on. *None: Users can turn on an outlet even if the device is in Near Overload or Overload state. *On Near Overload: Users cannot turn on an outlet when the device is in Near Overload or Overload state. *On Overload: Users cannot turn on an outlet when the device is in Overload state. Power Restore Peak Load Reset the peak load to zero. Energy Reset the energy to zero. ColdStart Configuration ColdStart State ColdStart Delay *Previous State: Outlets will return to the same state (on or off) they were in prior to the PDU turning off. The ColdStart Delay setting will apply when the PDU resumes power. *All On: All outlets will turn on when power is restored to the PDU. *Instant: Outlets will be turned on immediately when power is restored to the PDU. *Wait: Outlets will be turned on according to this setting when power is restored to the PDU. *Never: Outlets will not be turned on when power is restored to the PDU. System Configuration Idle Time The PDU LCD screen will turn off automatically after it remains idle for the selected period of time. **For some models, the Outlet Restriction only shows in the Bank Manager Page. Intelligent PDU User Guide 23