CyberPower PDU41102 User Manual 2 - Page 88
oltcfg index all show, oltcfg index 1 name test_1, oltcfg index 2 td_on 3, oltcfg index 3 td_off 3,
View all CyberPower PDU41102 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 88 highlights
Commad Line Interface Example 1: To display all outlet configuration CyberPower > oltcfg index all show Example 2: To name outlet #1 as test_1 CyberPower > oltcfg index 1 name test_1 Example 3: To set turn on delay of outlet #2 as 3 seconds CyberPower > oltcfg index 2 td_on 3 Example 4: To set turn off delay of outlet #3 as 3 seconds CyberPower > oltcfg index 3 td_off 3 Example 5: To set reboot duration of outlet #4 as 5 seconds CyberPower > oltcfg index 4 td_reboot 5 Example 6: To name outlet #1 as test_1, set turn on delay as 3 seconds, set turn off delay as 4 seconds and set reboot duration as 5 seconds with a single command CyberPower > oltcfg set 1 test_1 3 4 5 oltloadcfg Description: Show and set outlet load threshold, reset power parameters in outlet level. Option show guest index name overload nearover lowload pwrrest Example 1: Argument Description Show information of Outlet threshold. 1 | 2 | 3 Set daisy chain index. 1 | 2 |...|outlet number | all Select outlet index. Modify outlet name. Set outlet overload threshold value. Set outlet near overload threshold value. Set outlet low load threshold value. peakload | energy Reset the peak load or energy of outlet. Intelligent PDU User Guide 86