CyberPower PDU41102 User Manual 2 - Page 24

PDU Tab > Device Manager, PDU Tab > Manager > Device

Page 24 highlights

Web Interface Power Protection The configurable load threshold can be set to prevent an overload condition. Coldstart and system configurations are also offered for different user needs. See PDU Tab > Device Manager. PDU Tab > Manager > Device Item HOST/GUEST# Load Configuration Overload Threshold Near Overload Threshold Definition Select the role of PDU (HOST or GUEST#) if PDUs are daisy chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU. Set the value for the total current on the PDU that will signal an overload warning. Must be higher than Near Overload Threshold and equal to or lower than the PDU Rating in the Summary Tab. Set the value for the total current on the PDU that will signal a near overload warning. Must be between Overload Threshold and Low Load Threshold. Intelligent PDU User Guide 22

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124

22
Web Interface
Intelligent PDU User Guide
Power Protection
The configurable load threshold can be set to prevent an overload condition. Coldstart and system
configurations are also offered for different user needs. See
PDU Tab > Device Manager
.
PDU Tab > Manager > Device
Item
Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Load Configuration
Overload Threshold
Set the value for the total current on the PDU that will signal an
overload warning. Must be higher than
Near Overload Threshold
and equal to or lower than the PDU
Rating
in the
Summary Tab
.
Near Overload
Threshold
Set the value for the total current on the PDU that will signal a near
overload warning. Must be between
Overload Threshold
and
Low
Load Threshold
.