Option, Argument, Description
View all CyberPower PDU41102 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 86 highlights
Commad Line Interface To set near overload threshold at 10A CyberPower > devcfg nearover 10 Example 4: To set cold start delay at 0 CyberPower > devcfg coldstadly -1 Example 5: To set idle time of the device at 10 minutes CyberPower > devcfg idletime 10 bankcfg Description: Show and set bank load configuration. Option show guest index overload nearover lowload restriction Argument Description Show information of bank load threshold. 1 | 2 | 3 Set daisy chain index. b1 | b2 | all Select bank index. Set bank overload threshold value. Set bank near overload threshold value. Set bank low load threshold value. none | onnear | onover Set outlet restriction of bank Example 1: To display bank load configuration CyberPower > bankcfg show Example 2: To set overload threshold of bank 1 at 15A CyberPower > bankcfg index b1 overload 15 Example 3: To set near overload threshold of bank 2 at 10A CyberPower > bankcfg index b2 nearover 10 oltsta Description: Show information of outlet status. Option show guest Argument 1 | 2 | 3 Description Show information of outlet status. Set daisy chain index. Intelligent PDU User Guide 84