HP ProLiant ML310e HP ProLiant Gen8 Troubleshooting Guide Volume I: Troublesho - Page 56

Network controller or FlexibleLOM problems

Page 56 highlights

Network controller or FlexibleLOM problems Network controller or FlexibleLOM is installed but not working Action: 1. Check the network controller or FlexibleLOM LEDs to see if any statuses indicate the source of the problem. For LED information, see the network controller or server documentation. 2. Be sure no loose connections (on page 16) exist. 3. Be sure the correct cable type is used for the network speed or that the correct SFP or DAC cable is used. For dual-port 10-GB networking devices, both SFP ports should have the same media (for example, DAC cable or equal SFP+ module). Mixing different types of SFP (SR/LR) on a single device is not supported. 4. Be sure the network cable is working by replacing it with a known functional cable. 5. Be sure a software problem has not caused the failure. For more information, see the operating system documentation. 6. Be sure the server and operating system support the controller. For more information, see the server and operating system documentation. 7. Be sure the controller is enabled in RBSU. 8. Be sure the server ROM is up to date. 9. Be sure the controller drivers are up to date. 10. Be sure a valid IP address is assigned to the controller and that the configuration settings are correct. 11. Run Insight Diagnostics ("HP Insight Diagnostics" on page 68) and replace failed components as indicated. Network controller or FlexibleLOM has stopped working Action: 1. Check the network controller or FlexibleLOM LEDs to see if any statuses indicate the source of the problem. For LED information, see the network controller or server documentation. 2. Be sure the correct network driver is installed for the controller and that the driver file is not corrupted. Reinstall the driver. 3. Be sure no loose connections (on page 16) exist. 4. Be sure the network cable is working by replacing it with a known functional cable. 5. Be sure the network controller or FlexibleLOM is not damaged. 6. Run Insight Diagnostics ("HP Insight Diagnostics" on page 68) and replace failed components as indicated. Network controller or FlexibleLOM stopped working when an expansion board was added Action: 1. Be sure no loose connections (on page 16) exist. 2. Be sure the server and operating system support the controller. For more information, see the server and operating system documentation. Hardware problems 56

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102

Hardware problems 56
Network controller or FlexibleLOM problems
Network controller or FlexibleLOM is installed but not working
Action
:
1.
Check the network controller or FlexibleLOM LEDs to see if any statuses indicate the source of the
problem. For LED information, see the network controller or server documentation.
2.
Be sure no loose connections (on page
16
) exist.
3.
Be sure the correct cable type is used for the network speed or that the correct SFP or DAC cable is used.
For dual-port 10-GB networking devices, both SFP ports should have the same media (for example,
DAC cable or equal SFP+ module). Mixing different types of SFP (SR/LR) on a single device is not
supported.
4.
Be sure the network cable is working by replacing it with a known functional cable.
5.
Be sure a software problem has not caused the failure. For more information, see the operating system
documentation.
6.
Be sure the server and operating system support the controller. For more information, see the server and
operating system documentation.
7.
Be sure the controller is enabled in RBSU.
8.
Be sure the server ROM is up to date.
9.
Be sure the controller drivers are up to date.
10.
Be sure a valid IP address is assigned to the controller and that the configuration settings are correct.
11.
Run Insight Diagnostics ("
HP Insight Diagnostics
" on page
68
) and replace failed components as
indicated.
Network controller or FlexibleLOM has stopped working
Action
:
1.
Check the network controller or FlexibleLOM LEDs to see if any statuses indicate the source of the
problem. For LED information, see the network controller or server documentation.
2.
Be sure the correct network driver is installed for the controller and that the driver file is not corrupted.
Reinstall the driver.
3.
Be sure no loose connections (on page
16
) exist.
4.
Be sure the network cable is working by replacing it with a known functional cable.
5.
Be sure the network controller or FlexibleLOM is not damaged.
6.
Run Insight Diagnostics ("
HP Insight Diagnostics
" on page
68
) and replace failed components as
indicated.
Network controller or FlexibleLOM stopped working when an expansion board was
added
Action
:
1.
Be sure no loose connections (on page
16
) exist.
2.
Be sure the server and operating system support the controller. For more information, see the server and
operating system documentation.