>_]]VbTZR\ _^UZdZ_^Vb Failure 11: Low pressure switch failure Reason: 1. Too low system pressure causes that the unit stops and the compressor protection works, the failure can be resumed. 2. Pressure switch wire is not fixed well or in open circuit. start check if the connector between pressure switch and PCB is no fixed badly or damaged (CN20 on PCB) yes replace pressure switch connector, shut off and be electrified again, re-check check if the 2 straight lugs on no the pressure switch work badly yes replace pressure switch connector, shut off and be electrified again, re-check if indoor fan motor cannot startup normally no in heating mode(except for defrost) replace main control board and check again yes check if the indoor motor has no power input replace indoor motor and check again -100-