Haier 3U19FS1ERA Service Manual - Page 37

U19FS1ERA

Page 37 highlights

4.3 Limitation values on pipe installation 3U19FS1ERA >_]]VbTZR\ _^UZdZ_^Vb Item A,B,C liquid pipe A,B,C Gas pipe L1 (one way) L2 (one way) L3 (one way) L1+L2+L3 h H+ H- Unit Description Standard Maximum mm Size of the liquid side connection pipe φ6.35 / mm Size of the gas side connection pipe m Max.piping length between IU and OU of the way m Max.piping length between IU and OU of the way m Max.piping length between IU and OU of the way m Total liquid piping length m Drop between every two indoor units when the location of the outdoor unit is among indoor units m Drop between every two indoor units when the location of the outdoor unit is at one side of indoor units φ9.52 ≤10 ≤10 ≤10 ≤30 ≤1 ≤1 / ≤25 ≤25 ≤25 ≤50 ≤15 ≤7.5 m Drop between the outdoor unit and the indoor unit ≤5 ≤15 m Drop between the outdoor unit and the indoor unit when the location of outdoor unit is among the indoor units ≤5 m Drop between the outdoor unit and the indoor unit when the location of outdoor unit is at one side of indoor units ≤5 ≤7.5 ≤15 -37-

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137

±²³³´µ¶·¸¹ º·µ ±²»¼·½·²»´µ
3U19FS1ERA
4.3 Limitation values on pipe installation
Item
Unit
Description
Standard Maximum
A,B,C liquid pipe
mm
Size of the liquid side connection pipe
φ
6.35
/
A,B,C Gas pipe
mm
Size of the gas side connection pipe
φ
9.52
/
L1 (one way)
m
Max.piping length between IU and OU of the way
10
25
L2 (one way)
m
Max.piping length between IU and OU of the way
10
25
L3 (one way)
m
Max.piping length between IU and OU of the way
10
25
L1+L2+L3
m
Total liquid piping length
30
50
m
Drop between every two indoor units when the
location of
the outdoor unit is among indoor units
1
15
m
Drop between every two indoor units when the location of
the outdoor unit is at one side of indoor units
1
7.5
H+
m
Drop between the outdoor unit and the indoor unit
5
15
m
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is among the indoor units
5
7.5
m
Drop between the outdoor unit and the indoor unit when the
location of outdoor unit is at one side of indoor units
5
15
h
H-