Haier 3U19FS1ERA Service Manual - Page 37
U19FS1ERA
View all Haier 3U19FS1ERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 37 highlights
4.3 Limitation values on pipe installation 3U19FS1ERA >_]]VbTZR\ _^UZdZ_^Vb Item A,B,C liquid pipe A,B,C Gas pipe L1 (one way) L2 (one way) L3 (one way) L1+L2+L3 h H+ H- Unit Description Standard Maximum mm Size of the liquid side connection pipe φ6.35 / mm Size of the gas side connection pipe m Max.piping length between IU and OU of the way m Max.piping length between IU and OU of the way m Max.piping length between IU and OU of the way m Total liquid piping length m Drop between every two indoor units when the location of the outdoor unit is among indoor units m Drop between every two indoor units when the location of the outdoor unit is at one side of indoor units φ9.52 ≤10 ≤10 ≤10 ≤30 ≤1 ≤1 / ≤25 ≤25 ≤25 ≤50 ≤15 ≤7.5 m Drop between the outdoor unit and the indoor unit ≤5 ≤15 m Drop between the outdoor unit and the indoor unit when the location of outdoor unit is among the indoor units ≤5 m Drop between the outdoor unit and the indoor unit when the location of outdoor unit is at one side of indoor units ≤5 ≤7.5 ≤15 -37-