Haier 3U19FS1ERA Service Manual - Page 87

Max. 9 minutes E

Page 87 highlights

>_]]VbTZR\ _^UZdZ_^Vb After oil return in cooling mode, the quit condition of refrigerant eliminated: 1 minute later after oil return is over & Td‐Tc>30℃ OR OR Ts‐Tc2AVE>30℃ Tc2AVE<‐35℃ Max. 10 minutes Oil return procedure in heating mode: Send oil return signal oil return begins oil return over Inverter compressor indicated FQCY 60s oil return FQCY 60s soft startup Outdoor motor 0HZ AUTO 5s AUTO (TC control) 0HZ AUTO 4-way valve ON OFF 450pulse All expansion valves auto angle 350pulse(E) 15s 450pulse auto angle All indoors ON OFF anti-freezed startup Quit condition of oil return: Max. 9 minutes (E) OR OR Td‐Tc<20℃ for 30s continuously(5 minutes later, begin to count) & Ts‐Tc2AVE<15℃for 30s continuously(5 minutes later, begin to count) Running for min. 5 minutes(E) -86-

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137

After oil return in cooling mode, the quit condition of refrigerant eliminated:
1 minute later after oil return is over
Td
Tc
30
OR
OR
Ts
Tc2AVE
30
Tc2AVE
35
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return:
Max. 9 minutes (E)
OR
OR
Td
Tc
20
for 30s continuously(5 minutes later, begin
to count)
Ts
Tc2AVE
15
for 30s continuously(5 minutes later,
begin to count)
Running for min. 5 minutes(E)
Send oil return signal
oil return begins
oil return over
Inverter compressor
indicated FQCY
60s
oil return FQCY
60s
soft startup
0HZ
0HZ
5s
Outdoor motor
AUTO
AUTO
AUTO (TC control)
4-way valve
ON
OFF
15s
450pulse
450pulse
350pulse(E)
All expansion valves
auto angle
auto angle
All indoors
ON
OFF
anti-freezed startup
±²³³´µ¶·¸¹ º·µ ±²»¼·½·²»´µ
-86-