HP StorageWorks 2/16V HP StorageWorks SAN Switch 2/8V, 2/16V, 2/16N and 4/32 I - Page 103
Facility requirements, Table 28 Facility requirements - 32 switch
View all HP StorageWorks 2/16V manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 103 highlights
Facility requirements To ensure correct operation of the switch, the facility where the switch is in use must meet the requirements shown in Table 28. Table 28 Facility requirements Type Requirements Electrical Primary AC Input 100-240 VAC, 1.5A, 47-63 Hz (SAN Switch 2/8V) and 100-240 VAC, 2.0A, 47-63 Hz (SAN Switch 2/16V and SAN Switch 2/16N) and 47-63Hz (SAN Switch 4/32) switch autosenses input voltage Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the switch nameplate Circuit protected by a circuit breaker and grounded in accordance with local electrical codes. Thermal SAN Switch 2/8V, SAN Switch 2/16V, SAN Switch 2/16N: A minimum air flow of 24 cubic ft/minute available in the immediate vicinity of the switch SAN Switch 4/32: A minimum air flow of 47 cubic ft/minute available in the immediate vicinity of the switch Ambient air temperature not exceeding 40× C (104× F) while the switch is operating Cabinet (when rack-mounted) One rack unit in a 19-in. (48.3 cm.) cabinet All equipment in cabinet grounded through a reliable branch circuit connection Additional weight of switch must not exceed the cabinet's weight limits Cabinet must be secured to insure stability in case of unexpected movement, such as an earthquake SAN Switch 2/8V, 2/16V, 2/16N and 4/32 installation guide 103