Dell FC4500 Reference Guide - Page 97
Operating Limits, Requirement, Description
View all Dell FC4500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 97 highlights
Technical Specifications and Operating Limits A Operating Limits The ambient temperature specification is measured at the front door inlet. The site must have air conditioning of the correct size and placement to maintain the specified ambient temperature range. The air conditioning must be able to handle the BTU requirements of the DPEs. Requirement Ambient temperature Temperature gradient Relative humidity Elevation Drive module power Description 10°C to 40°C (50°F to 104°F) 10°C/hr (50°F/hr) 20% to 80% noncondensing 2438 m (8,000 ft) at 40°C; 3077 m (10,000 ft) at 37°C 25 W drive slot maximum (seeking) The operating limits listed above for temperature and humidity must not be exceeded inside the closed cabinet in which the DPE and any DAEs are mounted. Mounting equipment in a cabinet directly above or below a DPE does not restrict air flow to the DPE because air flows through the DPE from front to back. Cabinet doors must not impede the front-to-back air flow. Operating Limits A-5