Dell PowerEdge R340 EMC PowerEdge R340 Installation and Service Manual - Page 109
Table 35. Particulate contamination specifications, or MERV13 filtration.
![]() |
View all Dell PowerEdge R340 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 109 highlights
Table 35. Particulate contamination specifications Particulate contamination Air filtration Conductive dust Corrosive dust Specifications Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and nondata center environments. • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and nondata center environments. Table 36. Gaseous contamination specifications Gaseous contamination Copper Coupon Corrosion Silver Coupon Corrosion Specifications