Fluke 1625 FE 1625 Users Manual - Page 25
Selective Measurement of the Earthing Resistance (RE(), Measuring, Range, Display Range, Resolution
View all Fluke 1625 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
Earth/Ground Tester Specifications Selective Measurement of the Earthing Resistance (REA) Measuring method: Current and voltage measurement with probe as per EN61557-5 and current measurement in the individual branch with additional current transformer (patent applied for). Open circuit voltage: 20 / 48 V AC Short circuit current: 250 mA AC Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatically (AFC), 55 Hz (R*) Noise rejection: 120 dB (16 2/3 , 50 , 60 , 400 Hz) Max. overload: max. Urms = 250 V (measurement will not be started) Measuring Range Display Range Resolution Intrinsic Error * Operating Error * 0.001...2.999 Ω 0.001 Ω 3.00...29.99 Ω 0.01 Ω 0.020 Ω... 30 kΩ 30.0...299.9 Ω 0.300...2.999 kΩ 0.1 Ω 1 Ω ± (7 % of m.v. +2 digit) ± (10% of m.v. +5 digit) 3.00...29.99 kΩ 10 Ω * With recommended current clamps / transformers. Additonal error because of probe- and auxiliary earth typ.electrode resistance: RH (RS + 2000Ω) ×1.25 ×10−6% + 5digits RETOTAL Measuring error of RH and RS: typ.of 10% of RETOTAL + RS + RH Measuring time: typ. 8 sec. with a fixed frequency 30 sec.max. with AFC and complete cycle of all measuring frequencies 17