Cisco 10720 Configuration Guide - Page 60
Cable Lug, Crimping the Lug, grounding and bonding connectors.
View all Cisco 10720 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 60 highlights
Grounding the Cisco 10720 Internet Router Chapter 3 Installing the Cisco 10720 Internet Router Use a dual-hole cable lug to attach it to the chassis. Use two 6.3 mm (M6) screws on the 0.63-inch (16 mm) centers as shown in Figure 3-9, Figure 3-10, and Figure 3-11. The lug can be ordered from Cisco (Part Number 32-0607-01). Grounding connectors shall be NRTL listed; use copper conductors only for grounding and bonding connectors. Figure 3-9 Cable Lug 2.24 End View All measurements in inches 0.48 Ø 0.267 2 holes 0.25 0.63 0.37 0.08 Crimp area 25527 Figure 3-10 1 Crimping the Lug 57808 2 1 Place ground wire in the lug 2 Crimp the lug 3-10 Cisco 10720 Internet Router Installation and Configuration Guide 78-13062-10
3-10
Cisco 10720 Internet Router Installation and Configuration Guide
78-13062-10
Chapter 3
Installing the Cisco 10720 Internet Router
Grounding the Cisco 10720 Internet Router
Use a dual-hole cable lug to attach it to the chassis. Use two 6.3 mm (M6) screws on the 0.63-inch (16
mm) centers as shown in
Figure 3-9
,
Figure 3-10
, and
Figure 3-11
. The lug can be ordered from Cisco
(Part Number 32-0607-01). Grounding connectors shall be NRTL listed; use copper conductors only for
grounding and bonding connectors.
Figure 3-9
Cable Lug
Figure 3-10
Crimping the Lug
Crimp area
25527
2.24
0.48
0.08
0.25
0.37
0.63
End View
Ø 0.267
2 holes
All measurements in inches
1
Place ground wire in the lug
2
Crimp the lug
57808
2
1