Environmental, Gaseous Contamination, Copper Coupon Corrosion Rate
![]() |
View all Dell PowerVault DR6000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 105 highlights
Environmental Air Filtration Data center air filtration as defined by ISO Class NOTE: Applies to data center environments only. Air filtration requirements do not apply 8 per ISO 14644-1 with a 95% upper confidence limit. to IT equipment designed to be used outside NOTE: Air entering the data center must a data center, in environments such as an have MERV11 or MERV13 filtration. office or factory floor. Conductive Dust NOTE: Applies to data center and non-data center environments. Air must be free of conductive dust, zinc whiskers, or other conductive particles. Corrosive Dust NOTE: Applies to data center and non-data center environments. • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. Gaseous Contamination NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity. Copper Coupon Corrosion Rate Silver Coupon Corrosion Rate