HP 11kVA 400 Volt IEC309 16A 3-Phase Input 30xC13/3xC19 HP Monitored Power Dis - Page 106
Upgrading the HP Firmware with FTP Protocol, Uploading the Binary File
View all HP 11kVA 400 Volt IEC309 16A 3-Phase Input 30xC13/3xC19 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 106 highlights
Maintenance and Alarms Upgrading the HP Firmware with FTP Protocol The FTP upgrade requires the following steps. l In firmware mode, you upload a binary file that will be stored in the flash of the communications module. l In bootloader mode, the communications module automatically upgrades the firmware and the Web pages. Uploading the Binary File To access the Web interface: 1. Ensure that an Ethernet cable is correctly connected between a Windows PC and the Ethernet port on the PDU. Verify communication. 2. Start up the PDU and note the IP address displayed on the LCD. 3. Open an MS-DOS command line window and connect to the communications module in FTP mode (see Figure 51): l Type FTP @IP, where @IP is the previous IP address. l Type the user name and password of the SuperUser. l Type the hash command. This allows you to follow the upload as it progresses. 4. At the ftp> command line, use the put command with the Image.bin file to launch the upgrade (see Figure 51). Figure 51. Launching the Upgrade 5. Then the upgrade finishes, the closing message displays (see Figure 52). HP Monitored PDU User's Guide P-164000281-Rev 1 100