Tripp Lite PDU3VSR6L2130 Owner's Manual for SNMPWEBCARD 9332CE - Page 11
Actions > Event Actions > Device Actions
View all Tripp Lite PDU3VSR6L2130 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 11 highlights
3. Web Console continued 3.6 Actions Menu continued 3.6.1.1 Actions > Event Actions > Device Actions continued Device Shutdown Actions Device shutdown actions allow you to shutdown a device when a user-defined trigger occurs. Triggers include various alarms and even ENVIROSENSE readings. Device shutdown also includes the option to be put on a delay. To add an action, click the [+] button to activate a row and enter the appropriate data. To delete an action, click on the action that is to be deleted and then click the [-] button and confirm the deletion and then the [Save] button to commit the changes. Load Actions A load action is a device specific action that can be executed when an alarm trigger occurs. An example of a load action could be that when the device load goes above the user defined threshold and triggers a 'Load Level Above Threshold Event,' a specific load is turned off to reduce the load. The amount of controllable loads available on devices will vary from device to device. To add an action, click the [+] button to activate a row and enter the appropriate data. To delete an action, click on the action that is to be deleted and then click the [-] button and confirm the deletion and then the [Save] button to commit the changes. Figure 3-16: Device Shutdown Figure 3-17: Load Actions 11