Tripp Lite PDU3VSR6L2130 Owner's Manual for SNMPWEBCARD 9332CE - Page 38
Preferences and Thresholds
![]() |
View all Tripp Lite PDU3VSR6L2130 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 38 highlights
4. Telnet/SSH Console continued 4.1 Device Menu continued 4.1.5.3 Ramp/Shed Settings continued Menu Data Ramp Action This is the action to take when a ramp is initiated. The valid values are: • Remain Off • Turn On After Delay Ramp Delay This is the delay before taking the ramp action. Shed Action This is the action to take when a shed is initiated. The valid values are: • Remain On • Turn Off After Delay Shed Delay This is the delay before taking the shed action. 4.1.6 Preferences and Thresholds This menu contains the device and protocol specific data that defines the user's preferred behavior settings and thresholds. Since this menu is used to define the user's preferences, the values here should be editable. Preferences and Thresholds Menu -------- Preferences and Thresholds Auto Restart On Shutdown : Enabled Auto Restart On Delayed W : Enabled Auto Restart On Low Volta : Enabled Auto Restart On Overload : Disabled Auto Restart On Overtemp : Disabled 14 Day Self-Test : Disabled Watchdog Status : Disabled Watchdog Time : Disabled Low Battery Warning : % Low Battery Warning : 0.0 Years 1- Auto Restart On Shutdown 2- Auto Restart On Delayed Wakeup 3- Auto Restart On Low Voltage 4- Auto Restart On Overload 5- Auto Restart On Overtemp 6- 14 Day Self-Test 7- Low Battery Warning 8- Battery Age Alarm Threshold X- Device Main Menu M- Return to Main Menu Refresh Menu 38