Tripp Lite PDU3VSR6L2130 Owner's Manual for SNMPWEBCARD 9332CE - Page 32
Events
View all Tripp Lite PDU3VSR6L2130 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 32 highlights
4. Telnet/SSH Console continued 4.1 Device Menu continued 4.1.4 Events Events To access the events menu, the user must have at least Read access to the DEVICE EVENTS, ACTIONS and CONTACTS facilities in addition to the DEVICE STATUS facility. Events Summary Menu -------- Device Events Menu # | CATEGORY | DESCRIPTION | ENABLED 1 WARNING Load Level Above Threshold Yes 2 CRITICAL General Fault Yes 3 WARNING On Battery Yes 4 CRITICAL Output Source On Bypass Yes 5 CRITICAL Battery Bad Yes 6 CRITICAL Battery Low Yes 7 CRITICAL Overload Yes 8 WARNING Temperature High Yes 9 WARNING Battery Capacity Below Warning Yes 10 CRITICAL Output Off Yes 11 WARNING Self Test Failed Yes 12 INFORMATION Battery Age Above Threshold Yes 13 OFFLINE Communications Lost Yes 14 WARNING Loads Not All On Yes 15 WARNING Load 1 Off Yes 16 WARNING Load 2 Off Yes #- Select Event X- Device Main Menu M- Return to Main Menu Refresh Menu Event Details Menu -------- Device Event Menu Event Set Name : Load Level Above Threshold Event Clear Name : Load Level Below Threshold Event Category : WARNING Event Enabled : Yes Event Logging : On Set Action Clear Action Default Contact Notificat Default Contact Notificat Default Trap Notification Default Trap Notification Email to Admin Email to Admin 1- Manage Actions 2- Modify Event Category 3- Disable Event 4- Disable Logging for Event X- Device Events Menu M- Return to Main Menu 32