Panasonic WVCU360C WVCU360C User Guide - Page 70
DIP Switch Setting, Controller Number Setting, Switch Setting Procedures, Baud Rate Selection
UPC - 791871503454
View all Panasonic WVCU360C manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 70 highlights
s DIP Switch Setting An 8-bit DIP switch mounted on the rear panel specifies communication mode, etc. The default position is marked with an asterisk *. 78 78 456 456 23 23 901 CONTROLLER No. MODE DATA DC 9V IN Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Function System ID System ID System ID Reserved Line termination Operation mode Baud Rate Selection Repeat Transmissions OFF * * * * Off Operator* Auto-selection* 1 time* SW position ON See below See below See below Not used On* Administrator Set up from CU360 3 times s Controller Number Setting Set this switch always to 1 when using the System Controller in a System 850. 901 CONTROLLER No. q Switch Setting Procedures Set the MODE DIP switch and CONTROLLER NO. switch as follows. 1. Remove the DC plug from the rear of the controller. 2. Set the switches as follows. OFF ON 12 3 4 56 78 MODE • Bit 1 should be set to OFF*. • Bit 2 should be set to ON. • Bit 3 should be set to OFF*. • Bit 4 should be set to OFF*. • Bit 5 should be set to ON* when connecting with a System 850 in a home run (one to one) fashion. • Bit 6 should be set to OFF* (Operator) normally, or ON (Administrator) when setting up the controller. • Bit 7 should be set to ON. The baud rate is selected in the controller setup. • Bit 8 should be set to OFF* normally. 3. Connect the DC plug to the controller. 72