Honeywell HPF24S8 Installation Instructions - Page 29

Controlling Four Outputs With One Input

Page 29 highlights

Controlling Four NACs With One Input and Selective Silence Applications The control module is shown to demonstrate the use of a remotely mounted device associated with an addressable fire alarm control panel. The module could be replaced with any circuit capable of polarity reversal, such as an FACP NAC. Note: All NACs are supervised and power-limited ELR not required for Style Z (Class A) NAC Use listed ELR (4.7K) to terminate Style Y (Class B) NAC Horn/Strobes Alarm Polarity Shown Horn/Strobes Alarm Polarity Shown Style Z (Class A) Style Y (Class B) 24fsapp7tpH.wmf Internal Trouble Contact HPF24S ZNAC-4 Option Module Output/NAC 4 Output/NAC 3 Output/NAC 2 Output/NAC 1 HPF24S has been set for Selective Silence and Relay SW1 Switch Settings 1 & 2 = sync (any setting but OFF/OFF) 3 = OFF (master) 4 = OFF (no AC Fail reporting delay) 5 = ON 6 = ON (selective silence) SLC End-of-Line Resistor supplied with Control Module Module has been programmed at FACP as a silenceable point so it can perform selective silence when its Normally Open contact (7 & 9) closes in alarm, then opens when silence is SLC invoked at the FACP. Note: the Relay Module can be 7 = OFF (charger enabled) mounted on the power supply 8 = OFF (circuit 4 NAC function) Relay Module* Control Module* EOL Power Supervision Relay inside the cabinet. This allows power wiring to remain inside the cabinet. EOLR-1 *If the SLC device does not match the one in this figure, refer to (energized) the SLC manual appendix, which contains wiring conversion charts for type V and type H modules. Figure 5.1 Controlling Four Outputs With One Input Notes: The following notes apply to Figure 5.1 on page 29. 1. When the HPF24S power supply is in an inactive state (control module not active), a trouble on the power supply will result in an open circuit condition on the control module output circuit (monitored by End-of-Line Resistor across TB4, Terminals 5 & 6). As an alternative, the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring. 2. The addressable relay module must be programmed as a silenceable point at the FACP to allow selective silence of horn/strobe devices. The Normally Open contact of the relay module is connected between TB4 Terminal 7 (IN2 +) and Terminal 9 (Aux. Power +). 3. Do not loop wires under screw terminals. Break wires to maintain proper supervision. HPF24S Series Power Supplies - P/N 52751:D3 5/11/2010 29

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52

HPF24S Series Power Supplies —
P/N 52751:D3
5/11/2010
29
Controlling Four NACs With One Input and Selective Silence
Applications
The control module is shown to demonstrate the use of a remotely mounted device associated with
an addressable fire alarm control panel.
The module could be replaced with any circuit capable of
polarity reversal, such as an FACP NAC.
Notes: The following notes apply to Figure 5.1 on page 29.
1.
When the HPF24S power supply is in an inactive state (control module not active), a trouble
on the power supply will result in an open circuit condition on the control module output
circuit (monitored by End-of-Line Resistor across TB4, Terminals 5 & 6).
As an alternative,
the trouble contacts at TB5 of the power supply can also be used for independent trouble
monitoring.
2.
The addressable relay module must be programmed as a silenceable point at the FACP to allow
selective silence of horn/strobe devices.
The Normally Open contact of the relay module is
connected between TB4 Terminal 7 (IN2 +) and Terminal 9 (Aux. Power +).
3.
Do not loop wires under screw terminals.
Break wires to maintain proper supervision.
Figure 5.1
Controlling Four Outputs With One Input
Control Module*
Relay Module*
EOL Power
Supervision Relay
EOLR-1
(energized)
SLC
SLC
Style Z (Class A)
Style Y (Class B)
Use listed ELR
(4.7K
) to terminate
Style Y (Class B)
NAC
Note: All NACs are supervised and power-limited
ZNAC-4
Option Module
Output/NAC 4
Output/NAC 3
Output/NAC 2
Output/NAC 1
HPF24S has been set for
Selective Silence and Relay
Module has been programmed
at FACP as a silenceable point
so it can perform selective
silence when its Normally Open
contact (7 & 9) closes in alarm,
then opens when silence is
invoked at the FACP.
Note:
the Relay Module can be
mounted on the power supply
inside the cabinet.
This allows
power wiring to remain inside
the cabinet.
SW1 Switch Settings
1 & 2 = sync (any setting but OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = ON
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC function)
(selective silence)
End-of-Line Resistor
supplied with Control
Module
Internal Trouble Contact
ELR not required for
Style Z (Class A) NAC
HPF24S
Horn/Strobes
Alarm Polarity Shown
Horn/Strobes
Alarm Polarity Shown
24fsapp7tpH.wmf
*If the SLC device does not match the one in this figure, refer to
the SLC manual appendix, which contains wiring conversion
charts for type V and type H modules.