Honeywell HPF24S8 Installation Instructions - Page 36
Master HPF24S Power Supply Connected to FACP
View all Honeywell HPF24S8 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Applications Master HPF24S Power Supply Connected to FACP 5.6 Master HPF24S Power Supply Connected to FACP In this application, a master HPF24S power supply, set for synchronization, is connected to an FACP NAC with no synchronized output. Standby Polarity Shown 24fsapp11.cdr HPF24S Horn/Strobes (no synchronization) SW1 Switch Settings 1 & 2 = sync (any setting but OFF/OFF) 3 = OFF (master) 4 = OFF (no AC Fail reporting delay) 5 = 6 = OFF OFF general alarm 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) Figure 5.6 Supervised FACP to Master Connections Notes: The following notes apply to this Figure 5.6. 1. Refer to NFPA 72, Visible Characteristics, Public Mode. 2. Use only devices from the same manufacturer in each system. 36 HPF24S Series Power Supplies - P/N 52751:D3 5/11/2010