HP StorageWorks 2/128 HP StorageWorks SAN Director 2/128 Installation Guide, V - Page 165
Facility Requirements, Recommended power connector: IEC 320, EN60320 C19-Angled
View all HP StorageWorks 2/128 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 165 highlights
Technical Specifications Facility Requirements The facility housing the SAN Director 128 must meet the following requirements: ■ Power requirements: - Input power requirements: 200-240 VAC, 12A, 50-60 Hz - Recommended power connector: IEC 320, EN60320 C19-Angled, 16A/250VAC ■ Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the chassis nameplate ■ An air flow of at least 350 cubic feet per minute, available in the immediate vicinity of the SAN Director 2/128 ■ The power specifications listed in Table 20 ■ If the SAN Director 2/128 will be installed in an EIA rack, ensure the following: - All equipment installed in the rack has a reliable branch circuit ground connection, and does not rely on a connection to a branch circuit, such as a power strip. - The rack is balanced and mechanically secured to provide stability in the event of an earthquake. - Additional equipment does not exceed the rack's weight limits. SAN Director 2/128 Installation Guide 165