Located close to the 14U HP StorageWorks SAN Director 2/128 chassis, and easily accessible.
![]() |
View all HP StorageWorks 2/128 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 33 highlights
Installing and Configuring the SAN Director 2/128 ■ Ensure that two dedicated electrical branch circuits with the following characteristics are available for use: - 200 to 240 VAC, 50-60 Hertz. - Protected by a circuit breaker in accordance with local electrical codes. - Supply circuit, line fusing, and wire size that are adequate according to the electrical rating on the chassis nameplate. - Grounded outlets installed by a licensed electrician and compatible with the power cords. - Located close to the 14U HP StorageWorks SAN Director 2/128 chassis and easily accessible. Note: To maximize fault tolerance, connect each power cord to a separate power source. ■ Ensure the HP StorageWorks SAN Director 2/128 has access to a minimum airflow of 350 cubic feet per minute. ■ Ensure the air temperature measured at the blower inlet does not exceed 40 degrees Celsius during operation. SAN Director 2/128 Installation Guide 33