HP StorageWorks 2/128 HP StorageWorks SAN Director 2/128 Installation Guide, V - Page 37
Ensure that the switch fans have access to a total minimum air flow of 350
View all HP StorageWorks 2/128 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 37 highlights
Installing and Configuring the SAN Director 2/128 4. Verify that two dedicated electrical branch circuits are available, as follows: - 200 to 240 VAC, 50 to 60 Hz - Circuit breaker protection in accordance with local electrical codes - Supply circuit, line fusing, and wire size adequate to the electrical rating on the chassis nameplate - Easily accessible to the SAN Director 2/128 chassis - Grounded outlets installed by a licensed electrician, compatible with the power cords Note: To maximize fault tolerance, connect each power cord to a separate power source. 5. Ensure that the switch fans have access to a total minimum air flow of 350 cubic feet per minute (595 cubic meters per hour). 6. Ensure that the air intake and exhaust vents have a minimum of two inches of airspace. 7. Ensure that the air temperature on the air intake side is less than 40o Celsius (104o Farenheit) during operation. SAN Director 2/128 Installation Guide 37