Intel SR1600UR Service Guide - Page 111
Replacing a System Fan
![]() |
UPC - 735858206723
View all Intel SR1600UR manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 111 highlights
Replacing a System Fan Caution: The system fans are NOT hot-swappable. Before removing or replacing a fan, you must first take the server out of service, turn off all peripheral devices connected to the system, turn off the system by pressing the power button, and unplug the AC power cord from the system or wall outlet. Note: The fans that are integrated into the power supply cannot be replaced separately. If one of the fans in the power supply fails, the power supply must be replaced. The system fans at the front of the Intel® Server System SR1600UR can be individually replaced if one of them fails. Use the following steps to replace a dual rotor fan. 1. If installed, remove the PCI riser assembly. For instructions, see "Removing the PCI Riser Assembly" on page 41. 2. If installed, remove the processor air duct. For instructions, see "Removing the Processor Air Duct" on page 46. 3. Disconnect the fan cable from the backplane or fan board (see letter "A" in Figure 83). 4. Lift the failed fan from the module (see letter "B" in Figure 83 ). A B AF000368 Figure 83. Removing a Fan from the Fan Module 5. Position the replacement fan so the connector on the fan is at the right and pointing down. 6. With the fan oriented correctly, insert the fan into the fan module (see letter "A" in Figure 84), and insert the fan cable into the matching connector on the backplane or fan board (see letter "B" in Figure 84). Intel® Server System SR1600UR Service Guide 93