LG PQCPA11A0E Owner's Manual - Page 137

Setting the power control text, Desired power, Desired operation ratio, Operation switching period

Page 137 highlights

3. ACP operation by using the LG ACCS 3 Setting the power control (text) The setup item to set the wattage in kW or % is displayed at the right side of the peak operation ratio control screen. If it exceeds the setting value, the air conditioner is forcefully operated periodically according to the peak power operation rule. Desired power It displays the desired power in kW per hour to operate the peak operation function. Desired operation ratio It displays the desired power in % to operate the peak operation function. Operation switching period It displays the period to forcefully stop the operatioin. Caution: Setting the demand control Because the demand control is set by the externally connected demand controller, the items such as desired power, desired operation ratio and operation switching period can not be set wihin the LG ACCS program. Installation/Owner's Manual 3-55

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163

Installation/Owner's Manual
3-55
3. ACP operation by using the LG ACCS
Setting the power control (text)
The setup item to set the wattage in kW or % is displayed at the right
side of the peak operation ratio control screen.
If it exceeds the setting value, the air conditioner is forcefully operated
periodically according to the peak power operation rule.
3
Desired power
It displays the desired power in kW per hour to operate the
peak operation function.
Desired operation ratio
It displays the desired power in % to operate the peak
operation function.
Operation switching period
It displays the period to forcefully stop the operatioin.
Caution: Setting the demand control
Because the demand control is set by the externally connected demand controller, the
items such as desired power, desired operation ratio and operation switching period
can not be set wihin the LG ACCS program.