LG PQCPA11A0E Owner's Manual - Page 152

Caution: Maximum consumed power

Page 152 highlights

3. ACP operation by using the LG ACCS The information to set at the air conditioner (or ventilator) is as follows: Item Type Physical address Model name Maximum consumed power Description Type of indoor unit or ventilator. The indoor unit types to set are as follows: • UAC: Unified air conditioner This item is not set for the ventilator. Enter the physical address of the indoor unito or the ventilator. When [Default input] button is pressed, it is automatically created by inheriting the higher information. The physical address consists of three numbers. The first number and the second number are the G/W number and the outdoor unit number respectively, which can be set only within the information entered from the existing [G/W information] and [outdoor unit information]. The third number is the indoor unit or ventilator number, which can not be set overlapped within the same outdoor unit number and should be set within the range of 0~15. Enter the model name of the indoor unit or ventilator. Enter the maximum consumed power for the indoor unit or ventilator to use. The maximum consumed power depends on the model. Caution: Maximum consumed power Fi the peak/demand control function is used, the maximum consumed power for each indoor unit should be essentially entered. The consumed power of the air conditioner can be controlled not to exceed the setting value. How to display the consumed power of indoor unit Consumed power of the nth indoor unit (Consumed power of outdoor unit +Total consumed power of indoor unit) * = Consumed power of the nth indoor unit Total consumed power of indoor unit 3-70 ACP

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163

ACP
3-70
3. ACP operation by using the LG ACCS
The information to set at the air conditioner (or ventilator) is as follows:
Type
Type of indoor unit or ventilator.
The indoor unit types to set are as follows:
UAC: Unified air conditioner
This item is not set for the ventilator.
Physical address
Enter the physical address of the indoor unito or the ventilator.
When [Default input] button is pressed, it is automatically created by
inheriting the higher information.
The physical address consists of three numbers.
The first number and the second number are the G/W number and the
outdoor unit number respectively, which can be set only within the
information entered from the existing [G/W information] and [outdoor
unit information]. The third number is the indoor unit or ventilator
number, which can not be set overlapped within the same outdoor unit
number and should be set within the range of 0~15.
Model name
Enter the model name of the indoor unit or ventilator.
Maximum
Enter the maximum consumed power for the indoor unit or ventilator to
consumed power
use. The maximum consumed power depends on the model.
Item
Description
Caution: Maximum consumed power
Fi the peak/demand control function is used, the maximum consumed power for each
indoor unit should be essentially entered. The consumed power of the air conditioner
can be controlled not to exceed the setting value.
How to display the consumed power of indoor unit
Consumed power of the nth indoor unit
(Consumed power of outdoor unit +Total consumed power of indoor unit) *
Consumed power of the nth indoor unit
Total consumed power of indoor unit
=