Dell IP4700 Service Guide - Page 112
Operating Limits, Requirement, Description
View all Dell IP4700 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 112 highlights
Technical Specifications and Operating Limits A Operating Limits The ambient temperature specification is measured at the front door inlet. The site must have air conditioning of the correct size and placement to maintain the specified ambient temperature range. The air conditioning must be able to handle the BTU requirements of the IP4700. Requirement Ambient temperature Temperature gradient Relative humidity Elevation Drive module power Description 10°C to 40°C (50°F to 104°F) 10°C/hr (50°F/hr) 20% to 80% noncondensing 2438 m (8,000 ft) at 40°C; 3077 m (10,000 ft) at 37°C 25-W drive slot maximum (seeking) IMPORTANT: The operating limits listed above for temperature and humidity must not be exceeded inside the closed cabinet in which the IP4700 and any DAEs are mounted. Mounting equipment in a cabinet directly above or below a IP4700 does not restrict air flow to the file server because air flows through the IP4700 from front to back. Cabinet doors must not impede the front to back air flow. A-6 IP4700 Installation and Service Guide