Honeywell NX4S1 Installation Guide - Page 42
LANSRLU1 Connection
View all Honeywell NX4S1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 42 highlights
NetAXS™ NX4S1 Installation System Configuration 5.6 LANSRLU1 Connection This connection supports thirty-one panels for each drop line and a maximum of 255 IP connections. It has not been reviewed by UL. Note that PCI-2 units can also be wired anywhere along the drop line. See Figure 18 on page 28 and Figure 19 on page 29. Figure 22: LANSRLU1 Connection NIC Terminal HUB/SWITCH HUB/SWITCH RS-485 Cable RS485 NetAXS Panels Red/White Black/Green RS-485 COM TB7-1 (RS485+) TB7-2 (RS485-) TB7-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN) LANSRLU1 RJ-45 RS-232 (50 Ft.) See RS-485 Cable note EG EG) each NetAXS enclosure individually Only Earth Ground (EG) EG one side of cable EG 32 www.honeywell.com